Product description: Luminaires to be used in spaces with excessive vibration, such as bridges, industrial plants, tunnels, heavy machinery, railway facilities, tracks, oil platforms, and others, must be specifically designed to withstand demanding mechanical conditions. This implies complying with regulations and meeting technical characteristics that ensure safe, reliable, and long-lasting operation.
The requirements to be met are detailed below:
1. Minimum technical conditions for lighting systems in Colombia. RETILAP.
2. Technical requirements to ensure the safety of electrical installations. RETIE, NEC, NTC 2050.
3. Robust mechanical structure, die-cast aluminum or stainless-steel housing. IEC 60598-1, IEC 60598-2-3, IEC 60598-2-5.
4. Reinforced joints, no loose parts. IEC 60598-1, IEC 60598-2-3, IEC 60598-2-5.
5. Anti-loosening fasteners such as locknuts, spring washers, Grower washers, anaerobic adhesives, and others. IEC 60598-1, IEC 60598-2-3, IEC 60598-2-5, IEC 60068-2-6.
6. IP protection minimum IP65 or higher. RETILAP, IEC 60529 / EN 60529.
7. IK protection minimum IK08 or higher according to the area to be lit. RETILAP, IEC 62262 / EN 62262.
8. Temperature range -30°C to +50°C or more; this will depend on the installation site and the climatic environment. RETILAP, IEC 60598-1, IEC 60068-2-X.
9. Luminaire marking (as applicable). RETILAP, IEC 60598-1, NTC 2230.
10. Vibration resistance (low, medium, and high frequency). IEC 60598-1, UL 1598, ANSI C136.31, IEC 60068-2-6.
11. Electrical protection against overvoltage. RETILAP, IEC 60598-1, IEC 61000-4-5, ANSI C82.77-5-2015.
The requirements to be met are detailed below:
1. Minimum technical conditions for lighting systems in Colombia. RETILAP.
2. Technical requirements to ensure the safety of electrical installations. RETIE, NEC, NTC 2050.
3. Robust mechanical structure, die-cast aluminum or stainless-steel housing. IEC 60598-1, IEC 60598-2-3, IEC 60598-2-5.
4. Reinforced joints, no loose parts. IEC 60598-1, IEC 60598-2-3, IEC 60598-2-5.
5. Anti-loosening fasteners such as locknuts, spring washers, Grower washers, anaerobic adhesives, and others. IEC 60598-1, IEC 60598-2-3, IEC 60598-2-5, IEC 60068-2-6.
6. IP protection minimum IP65 or higher. RETILAP, IEC 60529 / EN 60529.
7. IK protection minimum IK08 or higher according to the area to be lit. RETILAP, IEC 62262 / EN 62262.
8. Temperature range -30°C to +50°C or more; this will depend on the installation site and the climatic environment. RETILAP, IEC 60598-1, IEC 60068-2-X.
9. Luminaire marking (as applicable). RETILAP, IEC 60598-1, NTC 2230.
10. Vibration resistance (low, medium, and high frequency). IEC 60598-1, UL 1598, ANSI C136.31, IEC 60068-2-6.
11. Electrical protection against overvoltage. RETILAP, IEC 60598-1, IEC 61000-4-5, ANSI C82.77-5-2015.